MU2000K, Universal Measuring Transducer, for AC- and DC- signals, cjurrent and voltage

Ready to ship today,
Delivery time appr. 1-3 workdays
- Part number: T236053
Measuring Transducer AC and DC, for Voltage and Current, scaleable
Measuring transducers MU2000K can measure DC- an AC-voltages up to 600 V and DC- and AC-currents 0-1/5 A.
Preset measuring ranges can be selected. More measuring ranges (zero and full-scale) can be easily scaled. The output signals DC 0/2-10 V and 0/4-20 mA are insulated from measuring input and supply voltage. With its universal supply voltage AC/DC 24-240 V the measuring transducer can be connected to all common supply voltages.
The MU2000K e.g. is suitable for measuring DC voltages and charging currents at batteries or for measuring AC voltages and currents in plants for own generation of energy.
Overview of functions
- Output signal 0-20mA and 0-10V or 4-20mA and 2-10V
- Rated Supply Voltage AC/DC 24-240V
- Insulation between inputs, outputs and supply voltage
Inputs
- AC/DC 0 … 600 V (preset values: 0…30 V / 80…120 V / 0…150 V / 0…300 V / 0…600 V)
- AC/DC 0 … 5 A (preset values: 0…1 A / 0…5 A)
- In measuring ranges for AC also DC-signals can be measured. Negative signals will be measured as positive signals.
Zeros and Full Scales for more measuring-ranges can be freely selected by the user.
Technical Data
Rated supply voltage Us
.......
AC/DC 24V-240 V, 0/50/60 Hz < 3 W < 8 VA
DC 20,4 - 297 V, AC 20 - 264 V
Input voltage
.......
AC/DC 0-30/150/300/600 V, 80-120 V, Ri = 500 kΩ, max. 600 V, max. 300 V to GND
Accuracy
.......
DC ≤ 0,2% AC ≤ 0,5% (50/60 Hz) from full scale, drift < 0,02 %K
Input current
.......
AC/DC 1A, 5A, max. 7,5A/4s, 25A/1s, 30 mΩ
Accuracy
.......
DC ≤ 0,2% AC ≤ 0,5% (50/60 Hz) from full scale, drift < 0,02 %K
Measuring method / Resoulution
.......
RMS (AC), averaging (DC), resolution 14 Bit
Output voltage
.......
DC 0/2-10 V, load min. 1 kΩ
Accuracy
.......
≤ 0,3 % from full scale, drift <0,01 %/K
Resolution
.......
11.6 Bit, <3,1 mV
Output current
.......
DC 0/4-20 mA, load max. 500 Ω
Accuracy
.......
≤ 0,3 % from full scale, drift <0,015 %/K
Resoulution
.......
11,6 Bit, <6,1 mA
Error load
.......
0,3 % of current x (250Ω - load) / 250Ω
Galvanic insulation
.......
Supply voltage - input - output
Measuring time / Averaging
.......
45 ms + 20 ms x number of averages (1/2/8/16/32 values)
Test conditions
.......
Rated ambient temperature range
.......
-20 °C ... +50 °C
Housing dimensions (h x w x d)
.......
design K, 75 x 22,5 x 115 mm
Protection housing/terminals
.......
IP 40 / IP 20
Attachment
.......
DIN rail 35 mm or screws M4
Weight
.......
ca. 100 g
Input / measuered parameter: | Voltage, Current measuring |
Outputs: | Analog output 0/4-20mA, 0-10V |
Design: | Mount in switchgear cabinet |
Approvals: | UKCA, UL/CSA |
Applications: | Plants for Generation of own Energy, Heat and power plants, Wind energy plants |