NS1, Level Monitor, 1 Limit, housing IP 54

Ready to ship today,
Delivery time appr. 1-3 workdays
- Part number: V223202
Level Monitor, Housing Design I94 IP54, 1 Niveau, 1 Limit, adjustable, Wall-mount
This level monitor for two electrodes preferrably serves to the limit control, e.g. as overflow or running dry protection of a conducting liquid. The device is integrated in a shock-resistant plastic housing of the type 94 and can also be used for outside- resp. waterproof mounting according to its protection system IP 54.
The function of the relay is reversible (standard: releases, when E2 is reached) by changing of jumpers in the device. The sensitivity can be changed between 25…250 kOhm and the switching delay between 0,5…10 s.
Technical Data
Supply Voltage Us
.......
AC 230 V
Adm. Tolerance Us
.......
+10%…-15%
Power Consumption
.......
≤ 3 VA
Frequency
.......
50…60 Hz
Relays
.......
1 CO
Contact type
.......
Type 2 (see General technical Informations)
Pick up delay
.......
approx. 0,5 s
Release delay
.......
approx. 0,5...10s adjustable
Text conditions
.......
see General technical Informations
max. ambient temperature
.......
-20°C...+55°C
Quantity Electrodes
.......
2
Voltage at the Electrodes
.......
< AC 6 Veff
Line capacity at 25 kΩ
.......
max. 100 nF = ca. 500 m
Line capacity at 150 kΩ
.......
max. 20 nF = ca. 100 m
Line capacity at 250 kΩ
.......
max. 10 nF = ca. 50 m
Dimensions (H x B x T)
.......
Design I 94: 94 x 94 x 57 mm
Fitting position
.......
with screws
Protection housing/ terminals
.......
IP 54/ IP 20
Weight
.......
approx. 310g
Input / measuered parameter: | Resistance/conductance |
Outputs: | Alarms/relays |
Design: | Wall-mount housing |