WD100V, Watchdog Time-Relay, Inputs clock 5/24 V, 0,5 - 10.000 ms

WD100V_Produktfoto_ZIEHL_2017-10-06.png
Price after registration.

Delivery time on request

  • Z224319
Input square wave DC 5/24 V Monitoring interval 1 - 10.000 ms Housing V2, 35 mm Replaces WD100V,... more

Watchdog Time-Relay for industrial PCs (IPC)

 

In the control technology of today, the number of industrial PCs (IPC) partly with decentralized intelligence constantly increases.

Individual processes are controlled independent of each other. In case of failure or malfunction of one component, it can therefore be necessary to switch off the hardware of a complete machine or plant.
Time-Relay WD100V is used to make sure that because of malfunctions in the program flow, caused by short-term voltage interruptions for instance, no undefined status are created.

Changes Z224317 --> Z224319: input 5V, maximum pulse length up to 10 s, better temperature stability

Overview of functions:

  • Input-signal 5/24 V DC square wave
  • Minimum pulse length 500 μs
  • Maximum pulse length 10 s
  • Monitoring of positive and negative slopes
  • Watchdog-time = Time x Scale (1 ms-10 s)
  • Display of state of function with LED (Alarm)
  • Reset with external contact or switch
  • Universal power-supply AC/DC 24-240 V
  • Relay-output (1 change-over contact)

 

Technical Data

Rated supply voltage Us

.......

AC/DC 24-240 V, 0/50/60 Hz, <2W, < 3 VA
DC 20,4-297 V, AC 20-264 V

 

Contact elements

.......

1 change-over contact (co)

 

Contact type

.......

Type 3 see general technical information

 

Measuring input clock

.......

app. DC 5/24 V square wave
Relay picked up when square wave voltage is fed
Relay is released 1-10.000 ms after last slope

 

Pulse length

.......

0,5 ... 10.000 ms

 

Input Reset

.......

Button for Reset / bridge = autoreset

 

Rated ambient temp. range

.......

-32°C...+70°C

 

Dimensions h x w x d

.......

Design V2: 90 x 35 x 58 [mm]

 

Weight

.......

approx. 100 g

 

Attachment

.......

on 35 mm DIN rail or with screws M4

 

Protection housing/terminals

.......

IP 30/ IP 20

 
Input / measuered parameter: Digital input
Outputs: Alarms/relays
Design: Mount in switchgear cabinet, Mount in circuit breaker box
Applications: Heat and power plants, Wind energy plants