TR210, Limit Value Switch, 2 inputs, transducer, Pt100/1000, KTY, TC, 0/4-20 mA, 0-10 V

Delivery time on request
- Part number: T224071
Limit Value Switch, 2 inputs, Pt100 (RTD), Pt 1000, KTY, TC, 0/4-20 mA, 0-10 V, 2-4 limits, analog output
The TR210 is used as
- General temperature protection of machines and installations
- Temperature control unit, also for cooling applications
- Difference temperature controller unit for air-conditioning technology
Overview of functions
- 2 Sensor inputs
- Pt 100, Pt 1000, KTY 83 or KTY 84 in 2- or 3-wire configuration
- Thermocouples Type B, E, J, K, L, N, R, S, T
- Input signal DC 0-10 V; DC 0/4-20 mA
- 0.1 °C resolution between –199.9...999.9 °C
- 2 Relay outputs (each 1 change-over contact)
- 1 Analogue output DC 0-10 V or 0/4-20 mA for parameterizing (not potentially separated from the inputs)
- Universal power supply AC/DC 24-240 V
- Several selectable programs
- Storage and indication of the measured MIN- und MAX-values
- pluggable terminals
- Accessory: Front mounting kit type ER4
- Alternative: Temperature relay Type TR640IP
Technical data
Rated supply voltage Us
.......
AC/DC 24 – 240 V
Tolerance DC
.......
20, 4 - 297 V
Tolerance AC
.......
20 - 264 V 50/60 Hz
Power consumption
.......
< 3 W < 7 VA
Relay output
.......
2 x 1 change-over contacts (CO)
Switching voltage
.......
max. AC 415 V
Switching current
.......
max. 5 A
Switching capacity
.......
max. 1250 VA (resistive load)
max. 120 W at DC 24 V
UL electrical ratings:
.......
250 V ac, 5 A, resistive
E214025
.......
240 V ac, 1/2 hp
120 V ac, ¼ hp
B 300 – pilot duty, UL 508
Housing
Enclosure
.......
Design V4, switchgear mounting
Mounting height
.......
55 mm
Width
.......
4 TE
Dimensions (width x height x depth)
.......
70 x 90 x 58 mm
Wire connection, one wire
.......
each 1 x 1.5 mm2
Stranded wire with insulated ferrules
.......
each 1 x 1.0 mm2
Torque
.......
0.5 Nm (3,6 lb.in)
Protection class housing
.......
IP 30
Protection class terminal
.......
IP 20
Installation
.......
Snap mounting on mounting rail 35 mm according to EN 60 715 or with screws M 4 (additional bar in scope of delivery)
Weight
.......
approx. 200 g
Input / measuered parameter: | Measuring Input Pt 100 (RTD), Measuring input other temperature sensors, Standard signals 0/4-20 mA, 0-10 V, Digital input |
Outputs: | Alarms/relays, Analog output 0/4-20mA, 0-10V |
Design: | Mount in switchgear cabinet, Mount in circuit breaker box |
Approvals: | UKCA, UL/CSA |
Extras: | 2-3 sensor inputs, Reclosing lock |
Applications: | Control for trace heating |